HVDC Cross-Channel

From Infogalactic: the planetary knowledge core
Jump to: navigation, search
Cross-Channel
Interconnexion France Angleterre
Sellindge Converter Station on the UK side of the interconnector
Sellindge Converter Station on the UK side of the interconnector
Location
Country France, United Kingdom
General direction south-north
From Bonningues-lès-Calais, France
Passes through English Channel
To Sellindge, United Kingdom
Ownership information
Partners National Grid plc, Réseau de Transport d'Électricité
Construction information
Manufacturer of conductor/cable Alstom
Manufacturer of substations ASEA (160 MW scheme); Alstom (2000 MW scheme)
Construction started 1985 (2000 MW scheme)
Commissioned 1986 (2000 MW scheme)
Technical information
Type submarine cable
Type of current HVDC
Total length Lua error in Module:Convert at line 1851: attempt to index local 'en_value' (a nil value).
Power rating 2,000 MW
AC Voltage 400 kV
DC Voltage ±270 kV
Number of poles 4 ( 2 bipoles)

The HVDC Cross-Channel (French: Interconnexion France Angleterre) is the name given to two different high voltage direct current (HVDC) interconnectors that operate or have operated under the English Channel between the continental European and British electricity grids.

The first Cross-Channel link was a 160 MW link completed in 1961 and decommissioned in 1984, while the second was a 2000 MW link completed in 1986.

The current 2000 MW link, like the original link, is bi-directional and France and Britain can import/export depending upon market demands.

160 MW system (1961)

The first HVDC Cross-Channel scheme was built by ASEA and went into service in 1961 [1] between converter stations at Lydd in England (next to Dungeness Nuclear Power Station) and Echinghen, near Boulogne-sur-Mer, in France. This scheme was equipped with Mercury arc valves, each having four anodes in parallel.[2]

In order to keep the disturbances of the magnetic compasses of passing ships as small as possible, a bipolar cable was used. The cable had a length of 65 kilometres (40 mi) and was operated symmetrically at a voltage of ±100 kV and a maximum current of 800 amperes. The maximum transmission power of this cable was 160 megawatts (MW). The cable was built by ABB Group.[citation needed] Given that the cable was laid on the surface of the seabed it was prone to being fouled by fishing nets, causing damage. Whilst repairs were undertaken there was considerable down time on the circuit resulting in a loss of trading. Indeed, by 1984 the circuit was disconnected from the Main Transmission System.

2000 MW system (1986)

Because the first installation did not meet increasing requirements, it was replaced in 1975–1986 by a new HVDC system with a maximum transmission rating of 2,000 MW between France and Great Britain, for which two new converter stations were built in Sellindge (UK) and in Bonningues-lès-Calais (Les Mandarins station), near Calais, (France). Unlike most HVDC schemes, where the two converter stations are built by the same manufacturer, the two converter stations of the 2,000 MW scheme were built by different manufacturers (although both have subsequently become part of the same parent company, Alstom). The Sellindge converter station was built by GEC[3] and the Les Mandarins converter station was built by CGE Alsthom.

This HVDC-link is 73 kilometres (45 mi) long in route, with 70 kilometres (43 mi) between the two ends. The undersea section consists of eight 46 kilometres (29 mi) long 270 kV submarine cables, laid between Folkestone (UK) and Sangatte (France), arranged as two fully independent 1,000 MW Bipoles, each operated at a DC voltage of ±270 kV. Cables are laid in pairs in four trenches so that the magnetic fields generated by the two conductors are largely cancelled. The landside parts of the link consist of 8 cables with lengths of 18.5 kilometres (11.5 mi) in England, and 6.35 kilometres (3.95 mi) in France.[4]

In common with the 1961 scheme, there is no provision to permit neutral current to flow through the sea. Although each station includes an earth electrode, this is used only to provide a neutral reference, and only one of the two electrodes is connected at a given time so that there can be no current flow between them.

The system was built with solid-state semiconductor thyristor valves from the outset. Initially these were air-cooled and used analogue control systems but in 2011 and 2012 respectively, the thyristor valves of Bipole 1 and Bipole 2 were replaced by more modern water-cooled thyristor valves and digital control systems supplied by Alstom.[5]

More than 25 years after originally being put into service, this system remains the world's largest-capacity submarine cable HVDC system.

Significance

Since the commissioning of the 2,000 MW DC link in the 1980s, the bulk of power flow through the link has been from France to Britain. However, France imports energy as needed during the winter to meet demand, or when there is low availability of nuclear or hydroelectric power.

As of 2005 imports of electricity from France have historically accounted for about 5% of electricity available in the UK. Imports through the interconnector have generally been around the highest possible level, given the capacity of the link. In 2006, 97.5% of the energy transfers have been made from France to UK, supplying the equivalent of 3 million English homes. The link availability is around 98%, which is among the best rates in the world. The continued size and duration of this flow is open to some doubt, given the growth in demand in continental Europe for clean electricity, and increasing electricity demand within France.[6]

Sites

Site Coordinates
Echingen converter station (out of service) Lua error in package.lua at line 80: module 'strict' not found.
Lydd converter station (out of service) Lua error in package.lua at line 80: module 'strict' not found.
Les Mandarins converter station Lua error in package.lua at line 80: module 'strict' not found.
Sellindge converter station Lua error in package.lua at line 80: module 'strict' not found.

See also

References

  1. Compendium of HVDC schemes, CIGRÉ, Compendium of all HVDC projects
  2. Cory, B.J., Adamson, C., Ainsworth, J.D., Freris, L.L., Funke, B., Harris, L.A., Sykes, J.H.M., High voltage direct current converters and systems, Macdonald & Co. (publishers) Ltd, 1965, p175–218.
  3. Rowe, B.A., Goodrich, F.G., Herbert, I.R., Commissioning the Cross Channel h.v.d.c. link, GEC Review, Vol. 3, No. 2, 1987.
  4. Compendium of HVDC schemes, CIGRÉ Technical Brochure No. 003, 1987, pp194–199.
  5. Lua error in package.lua at line 80: module 'strict' not found.
  6. http://webarchive.nationalarchives.gov.uk/tna/+/http://www.dti.gov.uk/files/file11257.pdf/

External links